SECTION 2
Mounting Instructions
Visit usa.siemens.com/versicharge for additional manuals and information.
2.1 Equipment List
2.1.1 Kit-Supplied Equipment
• 1 – VersiCharge (with optional NEMA 6-50 infrastructure plug for 40 A residential units only)
• 1 – Mounting bracket
• 1 – Cable holster
• 1 – Ferrite core
NOTE: Plug-supplied units (40 A) will have the ferrite core factory installed. Only units to be hardwired (48 A) will install the ferrite core.
• 1 – Multi-use connector (this connector is used to connect both the Modbus and the External Remote Control Interface
Connector)
NOTE: Supplied with commercial units only.
• RFID Cards: two admin cards and five user cards (supplied with commercial units only)
• 1 – Tamper-resistant 5/32" Allen wrench (for securing the charger)
• 1 – #8 x 2-1/2" flathead drywall screw (for securing the holster to the wall stud)
• 2 – Lag screws, hex head screws, 1/4 x 2" (for securing the mounting bracket to the wall studs)
• 2 – #10-32 X 3/8", tamper-resistant, pin-in-hex socket button head cap screw (for securing the charger)
2.1.2 Standard Installation Equipment
• Qualified electrician
• Cordless drill (Phillips bit with extender)–include 1/8" drill bit for pilot holes
• Stud finder
• 240 V AC voltmeter
• A 40 A charger requires a 2-pole, 240 V, 50 A circuit breaker. A 48 A charger requires a 2-pole, 240 V, 60 A circuit breaker.
• NEMA 6-50 outlet (if not hardwiring charger)
NOTE: Only used with the 40 A residential charger.
• 7/16" socket wrench
• Flathead screwdriver
NOTE: If using the wallboard mounting (alternate mounting) for the charger, a Phillips head screwdriver will also be needed.
• Tamper-resistant 5/32" hex bit with a ¼" Allen wrench (for securing the charger)
• If hardwiring the charger – #6 AWG 90 °C copper wire, three conductors – #6 AWG 90 °C copper wire should be used for a 48 A
charger, and #8 AWG 90 °C copper wire should be used for a 40 A charger.
NOTE: 1. Wire must have a temperature rating of 90 °C or higher. 2. Do not set the amp switch higher than 40 A unless
hardwired to a dedicated 60 A circuit according to national and local codes.
2.1.3 Alternate Installation Equipment (Screws and anchors are not included in the VersiCharge kit)
• 5 – #12 x 1-½ LG Phillips head Ø.375 head minimum, with five #12 wall anchors
NOTE: wall anchors must be rated for 61 lbs.for 1/2" dry wall.
Installation and Operations Manual VersiCharge™ AC