Siemens VersiCharge AC Installation And Operation Manual page 18

Electric vehicle charging station
Hide thumbs Also See for VersiCharge AC:
Table of Contents

Advertisement

VersiCharge™ AC Installation and Operations Manual
The VersiCharge comes set to the maximum of the model purchased. For example, a 40 A model will come with the amperage
adjustment switch set to 4, and a 48 A unit amperage adjustment switch will be set to 5. Verify the required amperage adjustment
switch setting based on the branch circuit protection (see the table below).
NOTE: The VersiCharge cannot control the power draw to the EV; it can only communicate the current capacity to the
VersiCharge to the EV.
3.2.1 Dial Settings
NOTE: The amperage adjustment dial is for use by a qualified technician/electrician only.
• When changing the amperage adjustment dial, verify that the VersiCharge is disconnected from power.
• The purpose of the amperage adjustment dial is to set the maximum current that the EV is allowed to
draw from the charging stations.
• The dial has 10 settings.
• Settings 0-5 are for amperage adjustments.
• Settings 6-9 are for factory use only. These settings will result in a bad switch fault if used.
Amperage Settings
Switch Position
0
1
2
3
4
5
NOTE: Do not set the switch above the 40 A unless
hardwired via the dedicated 60 A branch protection.
Settings: 0 - 4 amperage adjustment settings are used for
the 40 A charger (Note: the #5 position will cause a bad
switch fault for the 40 A charger) and 0 - 5 amperage
adjustment settings are used for the 48 A charger. Setting
the amperage adjustment higher than 5 will result in a
fault.
3.2.2 Circuit Requirements
• The circuit must be sized for the maximum ampere requirement. Do not derate breakers or conductors based on
amperage adjustment.
18
Amperage
12
16
24
32
40
48