Siemens VersiCharge AC Installation And Operation Manual page 16

Electric vehicle charging station
Hide thumbs Also See for VersiCharge AC:
Table of Contents

Advertisement

VersiCharge™ AC Installation and Operations Manual
NOTE: Plug removal is only necessary when hardwiring the VersiCharge.
NOTE: This enclosure has not been evaluated for rigid metallic and rigid non-metallic conduit. In order to maintain a Type
4 UL50E environmental rating, a hardwired installation should use liquid-tight flexible conduit only, with conduit glands
rated UL Type 4, 4X, 6 or 6P.
NOTE: Use flexible conduit only.
1.
The VersiCharge will need to be mounted on the bracket to hardwire the device. Access the back of the unit by shifting the
unit up and rotating it on the bracket hinges.
2.
Remove the high voltage door by releasing the snaps (use a flathead screwdriver if needed to assist).
Figure 7. Remove the plug
3.
Disconnect the attachment plug wires from the terminal block by loosening the screws in positions 1, 2 and 3, and remove the
ferrite core (the core will be reinstalled when hardwired).
4.
Do not adjust the two lugs of the pre-installed wiring. These are for factory use only.
5.
Disconnect and remove the strain relief and entire cord-and-plug assembly.
6.
Route the conductors into the VersiCharge from the conductor opening with proper strain relief.
7.
Pull 3-6 inches of slack through the conductor opening.
8.
Slide the ferrite core over the black and red wires ONLY and into position per Figure 8 (the green wire/ground
should not be placed through the ferrite core).
9.
Wire the conductors (copper only) into the VersiCharge (L1, L2 and Ground) from the connected conduit. Using a torque
screwdriver, torque all lugs to 14.5 lb.-in. See Appendix C for the hardwire bending diagram.
16