Physical Data; Electrical Data - Carrier Pro-Dialog Plus 30SZ Installation, Operation And Maintenance Instructions

Water-cooled/condenserless liquid chiller
Table of Contents

Advertisement

3 - PHYSICAL DATA

30SZ/SZV
Nominal cooling capacity
30SZ*
30SZV**
Operating weight
30SZ
30SZV
Refrigerant charge***
30SZ
Compressor type
No. of control steps
Capacity control
Evaporator type (30SZ/SZV)
Net water volume
Water connections
Inlet-outlet
Max. water pressure
Condenser type (30SZ)
Net water volume
Water connections
Inlet-outlet
Max. water pressure
*
Evaporator entering water temperature 12°C, evaporator leaving water temperature 7°C, condenser entering water temperature 30°C,
condenser leaving water temperature 35°C.
**
Evaporator entering water temperature 12°C, evaporator leaving water temperature 7°C; condensing temperature dewpoint 50°C.
*** The 30SZV units have a nitrogen holding charge only.

4 - ELECTRICAL DATA

30SZ
Nominal power supply
Voltage range
Nominal unit power input*
Nominal unit current drawn*
Maximum unit power input**
Maximum unit current drawn**
Starting current
30SZV
Nominal power supply
Voltage range
Nominal unit power input†
Nominal unit current drawn†
Maximum unit power input‡
Maximum unit current drawn‡
Starting current
*
Evaporator entering water temperature 12°C, evaporator leaving water temperature 7°C, condenser entering water temperature 30°C,
condenser leaving water temperature 35°C.
**
Evaporator leaving water temperature 10°C, condenser entering water temperature 50°C, condenser leaving water temperature 55°C.
Evaporator entering water temperature 12°C, evaporator leaving water temperature 7°C, condensing temperature dewpoint 50°C.
Evaporator leaving water temperature 10°C, condensing temperature dewpoint 60°C.
Electrical data notes
30SZ/SZV* units have a single power connection point.
The control box includes the following standard features:
-
the start-up and motor protection devices for each compressor.
-
the control devices
Field connections:
All connections to the system and the electrical installations must be in full
accordance with all applicable local codes.
The Carrier 30SZ/SZV units are designed and built to ensure con-formance
with these codes. The recommendations of European standard EN 60204-1
(corresponding to IEC 60204-1)-(machine safety - electrical machine compo-
nents - part 1: general regulations) are specifically taken into account, when
designing the electrical equipment.
Notes:
Conformance with EN 60204-1 is the best means of ensuring compliance with
the Machines Directive § 1.5.1. Generally the recommendations of IEC 60364
are accepted as compliance with the requirements of the installation
directives.
Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines.
1.
The operating environment for 30SZ/SZV units is specified below:
Environment* - Environment as classified in EN 60634 § 3:
-
ambient temperature range: +5°C to +40°C, class AA4*
-
humidity range (non condensable)*:
50% rh at 40°C
90% rh at 20°C
10
004
005
kW
14.60
16.10
kW
13.70
15.40
kg
105
110
kg
94
98
R-407C
kg
1.5
1.6
Scroll
1
1
%
-
-
Plate heat exchanger
l
1.23
1.42
MPT gas
in
1-1/4
1-1/4
kPa
1000
1000
Plate heat exchanger
l
1.23
1.42
MPT gas
in
1-1/4
1-1/4
kPa
1000
1000
004
005
V-ph-Hz
400-3-50
V
360-440
kW
3.88
4.06
A
6.85
6.95
kW
5.34
6.19
A
9.05
9.70
A
59.5
70.5
004
005
V-ph-Hz
400-3-50
V
360-440
kW
4.14
4.43
A
7.65
7.75
kW
4.44
5.10
A
9.05
9.70
A
59.5
70.5
006
007
009
19.50
22.90
27.90
18.50
22.10
26.40
116
144
168
102
129
150
2.20
2.16
2.30
1
1
1
-
-
-
1.71
1.90
2.37
1-1/4
1-1/4
1-1/4
1000
1000
1000
1.71
1.90
2.37
1-1/4
1-1/4
1-1/4
1000
1000
1000
006
007
009
011
6.03
7.03
7.33
9.89
10.75
12.45
13.70
15.70
8.51
10.00
10.87
13.31
14.10
16.50
18.00
21.16
94.0
116.0
127.0
159.0
006
007
009
011
6.36
7.32
8.02
10.70
11.70
13.50
15.45
17.50
6.77
7.53
9.29
11.34
14.10
16.50
18.00
21.16
94.0
116.0
127
159.0
-
altitude:
2000 m
£
-
indoor installation*
-
presence of water, class AD2* (possibility of water drops)
-
presence of hard solids, class AE2* (no significant dust present)
-
presence of corrosive and polluting substances, class AF1 (negligible)
-
vibration and shock, class AG2 , AH2
-
Competence of personnel, class BA4* (personnel trained in accordance
with IEC 60364)
2.
Power supply frequency variation: ± 2 Hz.
3.
The neutral (N) line must not be connected directly to the unit (if necessary
use a transformer).
4.
Overcurrent protection of the power supply conductors is not provided with the
unit.
5.
The factory-installed disconnect switch(es) is (are) of a type suitable for power
interruption in accordance with EN 60947-3 (corresponding to IEC 60947-3).
6.
The units are designed for connection to TN networks (IEC 60364). For IT
networks the earth connection must not be at the network earth. Provide a
local earth, consult competent local organisations to complete the electrical
installation.
NOTE: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should be
considered, always contact your local Carrier representative.
*
The required protection level for this class is IP21B (according to reference
document IEC 60529). All 30SZ/SZV units are protected to IP23C and fulfil this
protection condition.
011
018
024
027
33.50
56.00
78.00
85.00
32.30
52.00
72.00
77.00
182
424
480
492
162
390
441
448
2.97
8.10
9.00
10.20
Semi-hermetic
1
2
2
2
-
50-100
66-100
66-100
2.85
4.70
5.60
6.60
1-1/4
1-1/2
1-1/2
1-1/2
1000
1000
1000
1000
2.85
4.70
5.60
6.60
1-1/4
1-1/2
1-1/2
1-1/2
1000
1000
1000
1000
018
024
027
15.70
23.70
25.80
25.50
34.00
38.45
19.58
26.50
29.83
33.30
42.55
53.10
104.0
134.0
152.0
018
024
027
16.40
23.80
26.10
27.90
36.35
41.40
18.18
24.23
26.58
33.30
42.55
53.10
104.0
134.0
152.0
036
112.00
106.00
530
475
11.60
2
66-100
8.40
1-1/2
1000
8.40
1-1/2
1000
036
36.30
54.95
42.66
70.10
207.0
036
36.70
58.80
37.77
70.10
207.0