218If-01 Module - YASKAWA MP2000 Series Troubleshooting Manual

Hide thumbs Also See for MP2000 Series:
Table of Contents

Advertisement

1.4.3 218IF-01 Module

LEDs at the front of the Ethernet Module
RUN
STRX
TX
LED Indication
Cate-
Module Front
gory
RUN
ERR
Normal
Alarm
Error
Note:
: Unlit, : Lit,
ERR
COL
RX
COL
TX
RX
Operating normally
No Ethernet connection
/
Collision detected
Module fault
: Flashing, –: Indefinite
Indication
Normal operation is in progress.
Ethernet connection is not established.
Check the following.
• Ethernet cables are connected properly.
• Cables are not broken.
• The power to an Ethernet device such as a
hub that is connected directly to the Ethernet
Module with an Ethernet cable is turned on.
Transmission data collisions are occurring in
Ethernet communication. Reduce the load of
the network.
<Remedy example>
• Adjust the message transmission cycles.
• Use a switching hub.
Hardware failure has occurred.
Replace the Ethernet Module.
1.4 Checking the LED Indications

1.4.3 218IF-01 Module

Remedy
1
1-7