3.3 Message Communication Error
3.3.3 Checking the Message Function
( 3 ) Checking the Message Function Parameters
If message communication with the PLC or touch panel of another manufacturer or the computer does not start, the
message function may not have been executed properly due to incorrect setting of the message function parameters.
Check the settings of the message function parameters by following the procedure below.
Use the register list of MPE720 to check the data of the registers.
Execute
Abort
Dev-Typ
Pro-Typ
Cir-No
Ch-No
Param
DA00000
Example: When DA00000 was specified as the start address of the parameter list
3-20
MSG-SND
Busy
Complete
Error
Parameter List
Register
F
DW00000
PARAM00
DW00001
PARAM01
PARAM02
DW00002
DW00003
PARAM03
PARAM04
DW00004
DW00005
PARAM05
DW00006
PARAM06
DW00007
PARAM07
DW00008
PARAM08
DW00009
PARAM09
DW00010
PARAM10
DW00011
PARAM11
DW00012
PARAM12
DW00013
PARAM13
DW00014
PARAM14
DW00015
PARAM15
DW00016
PARAM16
Execute
Abort
Dev-Typ
Pro-Typ
Cir-No
Ch-No
Param
DA00000
0
MSG-RCV
Busy
Complete
Error