YASKAWA MP2000 Series Troubleshooting Manual page 43

Hide thumbs Also See for MP2000 Series:
Table of Contents

Advertisement

4.
Check the connection parameter settings.
Note: For the 218IF-02 and 218IF-01 Modules, Detail Setting is not displayed.
Setting Item
Local Port
Node IP Address
Node Port
Connect Type
Protocol Type
Code
Unpassive Open Mode
To use the unpassive open mode, set the connection parameters as follows.
INFO
• Set the remote station address (Node IP Address) to 000.000.000.000.
• Set the remote station port number (Node Port) to 0.
In the unpassive open mode, the Ethernet Module (built-in Ethernet, 218IF-02, or 218IF-01 Module) connects to any station that
attempted an access to the relevant connection number. If more than one station attempted an access, the connection will be
established with the station which transmitted the connection request first.
When a connection is established in the unpassive open mode, a connection request from another station breaks the current
connection and establishes the connection with the station that sent the connection request later.
• For a built-in Ethernet Module
Press the Detail Setting button to display the Automatically Reception dialog box.
When using the message function, select the Disable option.
Note: If the message function is used with the Enable option selected, communication may not be carried
out properly.
Connection Parameter Settings
Connection Parameter Check Items
Check Item
Set the transmission target port number to be used
by the remote station.
Set the IP address of the remote station.
Set the transmission source port number to be used
by the remote station.
Set the connection type of the remote station.
Set the protocol type that the remote station sup-
ports.
Set the code type of the remote station.
3.3 Message Communication Error
3.3.2 Checking the Connection Parameters
Remarks
Set 000.000.000.000 when using the
unpassive open mode.
If the port number of the remote station
will be changed dynamically, use the
unpassive open mode. To use the unpas-
sive open mode, set 0000.