X.limit - Limitation Of The Mechanical Valve Adjustment Range; Cutoff - Burkert 3281 Operating Instructions Manual

Motor valve
Hide thumbs Also See for 3281:
Table of Contents

Advertisement

Type 3281
Start-up
8.5.7

X.LIMIT - Limitation of the mechanical valve adjustment range

This function limits the (physical) control range to predetermined % values (bottom and top). The valve
adjustment range of the limited adjustment range is set equal to 100%. If the limited valve control range is left
during operation, negative actual positions or actual positions greater than 100% are displayed.
Factory setting: Limit bottom setting range = 0%, limit top setting range t = 100%
Setting ranges:
Limit bottom setting range:
limit top setting range:
Limited
Physical setting
setting range
range (%)
(%)
Fig. 15:
Diagram X.LIMIT
8.5.8

CUTOFF

CUTOFF_min - Sealing function for positioners/process controllers
This function ensures that the valve is tightly closed outside the control range Enter limits here for the set-
point position (CMD) or process set-point value from which the actuator is completely closed.
CUTOFF_max - Opening function for positioners/process controllers
This function ensures that the valve opens 100% outside the control range Enter limits for the set-point
position (CMD) or process set-point value from which the actuator opens completely.
0...20% of the total setting range
80...100% of the total setting range
Unlimited setting
range
Limited setting
range
Set-point value [mA](INPUT)
english
33