Please do not place the equipment in environment with extreme humidity and temperature
changes, dust, dirt, rubbles, paint, conductive particles or corrosive gases.
Do not remove the equipment packaging before installation.
The contractor receiving the equipment shall be responsible for equipment protection during
the storage period.
The equipment must be stored on a solid level floor.
Before the arrival of the equipment, an ambient temperature/humidity control plan shall be
formulated.
This product is suitable to be installed and used in the G1 environment provided in ANSI/ISA-
71.04-2013. Please see
Table 8-1: Gas concentrations recommended in Table B1 of ANSI/ISA-71.04-2013 for G1
equipment environment
Pollutants
Group A
Group B

Table 8-2: Requirements on the environment for transportation and storage within 1 year

Environment for transportation and storage within 1 year
(Subject to the production date on the label of equipment serial No.)
Storage site
Dust
Storage temperature
Storage humidity
Others
If the actual storage conditions of the machine do not meet the above storage environment, re-
evaluate the storage time according to the actual storage environment.
Copyright © 2022 Eaton Corporation plc. All rights reserved.
Table 8-1
for the gas concentration limits of relevant gases.
Gases
H
S
2
SO
SO
2
3
Cl
2
NO
x
HF
NH
3
O
3
Indoor
Good
< 40℃
< 70% RH
Stored with initial packaging
Eaton 93PR 15-80 kW UPS
Installation and Operation Manual
Gas concentration/ppbv
<3
<10
<1
<50
<1
<500
<2
82