Product overview
3.1 Properties of I/O module
Validity of safety parameters
The safety parameters in the technical specifications are valid for a mission time of 20 years and
a repair time of 100 hours. If a repair is not possible within 100 hours, remove the relevant
module from the terminal block or switch off its supply voltage before 100 hours elapse. After
100 hours elapse, the module switches off on its own.
For repairs, follow the procedure described in section "Diagnostic messages (Page 67)".
(FAIW-001)
Note
Cyclic reading of I&M data
Cyclic reading of I&M data can put a strain on the timing of the F-modules. Therefore, avoid fast
read cycles lower than 500 ms.
12
WARNING
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA