Applications of the F-I/O module

6.4 Application case 2: SIL3/Cat.3/PLd, 4-wire transducer, 1oo1

6.4
Application case 2: SIL3/Cat.3/PLd, 4-wire transducer, 1oo1
Definition
In the following, you can find the wiring diagram and the configuration of the I/O module F-AI
8xI 2-/4-wire HART HA for application case 2:
• SIL3/Cat.3/PLd
• 1oo1 evaluation
• 4-wire transmitter
You can find possible diagnostic messages, their causes and remedies in the "Diagnostic
messages" section.
Wiring
You perform the wiring on the appropriate terminal block. You can find more information on this
in the section "Terminal assignment (Page 17)".
Sensor supply
The sensor supply is external for a 4-wire transmitter.
Wiring scheme
Requirement for sensor
To achieve SIL3/Cat.3/PLd using this wiring, you must use a qualified sensor.
(FAIW-004)
44
WARNING
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA