Planning Your Configuration and Data Mapping Your Devices
Publication 1756-6.5.19 - May 2000

RediSTATION Operator Interface Data Mapping

The RediSTATION has both inputs and outputs that must be mapped.
The input byte is mapped to the 1756-DNB module's input data file
and then to the Logix5550 controller's input image table. The output
byte is mapped to the 1756-DNB module's output data file and then to
the Logix5550 controller's output image table.
The mapping procedure, using RSNetWorx for DeviceNet software, is
described on pages 4-15 to 4-18.
RediSTATION operator interface
Indicator light
green start light
red start light
The RediSTATION
operator interface
produces one byte of
input data and uses one
byte of output data.
In the RediSTATION's bits for the red and green buttons and the
indicator light status bit:
• 1 = ON
• 0 = OFF
Two input bits from the RediSTATION will
be mapped: bit 1 for the green Start button
and bit 0 for the red Stop button.
Bit 4 of the input byte can be commanded
on by the Logix 5550's ladder logic if the
indicator light bulb is burnt out or missing.
start bit (green button)
input
1 byte
7
6
5
4
3
2
blink bit for indicator light
output
1 byte
7
6
5
4
3
2
One output bit for the RediSTATION's
indicator light (on/off) will be mapped.
stop bit
G R
(red button)
1
0
output bit for
B
L
indicator light
1
0