Configuring the DeviceNet Network
Publication 1756-6.5.19 - May 2000
The resulting device mapping will appear in the lower panel:
Slot 1
Double word 0
I = Input
In chapter 3 the 1756-DNB module was installed in slot 1 in the
ControlLogix chassis. In this example the inputs from the
RediSTATION are mapped to double word 0 for slot 1 as bits 0-7 of
the low word (L). Recall from chapter 2 that the START button is bit
1 and the STOP button is bit 0. Therefore, the addresses for the
RediSTATION inputs are:
START Local:1:I.Data[0].1
STOP
Local:1:I.Data[0].0
The input from the photoeye is mapped to double word 0 for slot 1
as bits 8-15 of the low word. Recall from chapter 3 that the input bit
is bit 0. Therefore, the address of the photoeye input is:
Local:1:I.Data[0].8
3. Note the addresses assigned to the START and STOP buttons
and the photoeye in your system. You will use these addresses
in the example application program.
4. Select the Output tab.
Photoeye
RediSTATION
inputs
inputs