TYPE OF GAS MONITOR

Gas Type
Type of refrigerant gas.
18.15

ELECTRONIC VALVE NUMBER MONITOR

Number EEV
Number of electronic valves present.
18.16
GLYCOL WATER TEMPERATURE AND ENABLING
MONITOR
Glycolated water
management
Glycolated water
freezing temp.
Glycol water management enabling.
Water-glycol mixture freezing temperature (TCMA).
When the function is enabled, the following parameters are calculated automatical-
ly and cannot be changed:
— minimum limit of the cooling setpoint (TCMA + 4°C)
— antifreeze prevention setpoint (TCMA + 3.8°C)
— antifreeze alarm setpoint (TCMA + 3°C)
— antifreeze heater activation setpoint (TCMA + 3.5°C)
— cooling force-off setpoint (TCMA + 3.5°C)
18.17
R1234ze
— Serial address 1 for supervisor
— Speed of communication
— Type of protocol used for communication with the supervisor: Lon, pCOweb,
2
18.18
— Serial address 2 for supervisor
— Speed of communication
18.19
N
00.0 °C
Multifunction input (MASTER ONLY) on input B7 active on master.
Function:
— None: no functionality
— Setpoint: working setpoint selection
— Limit: limitation of the cooling capacity
— Demand: Cooling capacity request
— Comp.Ext: Setpoint compensation with temperature
Type:
— NTC: input with temperature and probe NTC10K
— 0-10V: input 0-10 volt dc
— 4-20mA: Input 4-20mA

BMS PARAMETERS MONITOR

supervisor
Address
Baudrate
Protocol
Modbus

BMS2 PARAMETERS MONITOR

supervisor
Address
Baudrate
Protocol

MULTIFUNCTION INPUT MONITOR

Probe 7 con g.
Function
Type
(BMS)
001
19200
Modbus
(BMS2)
001
19200
Modbus
None
NTC
35