Heating and cooling setpoint monitor
INSTALLER
6/8
Probe 7 Multifunction Con guration
Setpoint
Function
4.0
mA Low
mA
Setpoint Low
7.0
°C
Cooling
Setpoint Low
45.0
°C
Heating
Multifunction input enabled with Setpoint function:
— Cooling setpoint corresponding to the minimum size of the input
— Cooling setpoint corresponding to the maximum size of the input
— Heating setpoint corresponding to the minimum size of the input
— Heating setpoint corresponding to the maximum size of the input
Multifunction input with cooling capacity limit monitor
INSTALLER
6/8
Probe 7 Multifunction Con guration
Limit
Function
4.0
mA
mA Low
0
%
Limit Low
Multifunction input enabled with cooling capacity limit function:
— Power limit corresponding to the minimum size of the input
— Power limit corresponding to the maximum size of the input
Multifunction input with power request function monitor
INSTALLER
6/8
Probe 7 Multifunction Con guration
Demand
Function
4.0
mA
mA Low
0
%
Demand Low
Multifunction input enabled with power request function:
— Power request corresponding to the minimum size of the input
— Power request corresponding to the maximum size of the input
Multifunction input with setpoint compensation monitor (A)
INSTALLER
6/8
Probe 7 Multifunction Con guration
Compensation
Function
4.0
mA Low
mA
Compensation
7.0
°C
Low Cooling
Compensation
45.0
°C
Low Heating
10:45:44
4-20mA
Type
20.0
mA High
mA
Setpoint High
12.0
°C
Cooling
Setpoint High
50.0
°C
Heating
10:46:11
4-20mA
Type
20.0
mA High
mA
100
%
Limit High
10:46:34
4-20mA
Type
20.0
mA High
mA
100
%
Demand High
10:46:57
4-20mA
Type
20.0
mA High
mA
Compensation
12.0
°C
High Cooling
Compensation
50.0
°C
High Heating
Multifunction input enabled with setpoint compensation with temperature probe
function:
— Cooling setpoint compensation corresponding to the minimum size of the in-
1
put
— Cooling setpoint compensation corresponding to the maximum size of the in-
put
— Heating setpoint compensation corresponding to the minimum size of the in-
put
— Heating setpoint compensation corresponding to the maximum size of the in-
put
Digital contact enabling and setting monitor
7/8
Enable
Step 2
Pulldown Enable
Delay
1
Compressor
Power request enabling from digital contacts ID 16, ID 17, ID 18.
Digital contact power step setting:
— Power step 1 ID 16
— Power step 2 ID 17
— Power step 3 ID 18
Pull Down control:
— Enabling
— Water temperature variation rate below which the activation of new steps is
enabled
— Delay time between the activation of two subsequent steps
New password for gas alarm reset and installer menu monitor
8/8
Installer
Password
Alarm Reset
1
Password
— Entering a new password for gas alarm reset.
— Entering a new password for the installer menu.
1
INSTALLER
Digital Demand
Step 1
Step 3
75
%
Temperature
180
s
Rate
INSTALLER
0000
0000
10:47:38
1
40
%
100
%
1.0
°C/m
10:48:10
1
19