The alarms read by the compressor inverter card can have three levels, as indicated in the example window:
AL: XXX
Inverter
ALARM NAME
(Warning/Critical/Fault)
— Warning: pre-alarm condition
— Critical: becomes Fault after 30''
— Fault: compressor OFF manual reset alarm
42
Description
EVD - LOP 2 alarm
EVD - MOP 2 alarm
EVD - Low overheating 2
EVD - Low suction temperature 2
Inverter – envelop init error
Inverter – fault
Inverter – overcurrent
Inverter - over voltage
Inverter – over temperature
Inverter – under voltage
Inverter – power supply fault
Inverter – hardware fault
Inverter – temperature sensor fault
Inverter – hardware configuration error
Inverter – configuration data error
Inverter – configuration parameter error
Inverter – motor thermal overload
Inverter – motor overload
Inverter – motor phase failed
Inverter – high oil temperature
Inverter – low oil temperature
Inverter - Compressor Short Cycling
Inverter – envelope error
Inverter – serial control timeout
Inverter – communication error
Inverter – datalog error
Inverter – pressure sensor fault
U:01
Note
The compressor is working out of envelope
· inverter temperature too high
· check the liquid valve and/or refrigerant load. The valve activates
when the oil exceeds 100°C and deactivates when it goes below
95°C
· failure of a phase or imbalance between phases
· inverter temperature sensor fault. Check the oil sensor and motor
sensor
· incorrect hardware configuration
· incorrect software configuration
· incorrect inverter parameters
· motor winding temperature above limits
· high oil temperature (check oil heater)
- warning if greater than 115°C
- fault if greater than 120°C
- reset alarm if less than 105°C
· compressor starting is requested before the minimum time
between two starts has passed. This occurs only at the Warning level
The compressor is working out of envelope
· power request from card pCO5+ to inverter timeout
Type
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3