Outputs Configuration And Confirmation Of Configuration; Outputs Configuration For Fan Convector; Software Update - Plum ecoVENT MIDI Installation And Operating Manual

The controller with balanced ventilation function
Table of Contents

Advertisement

19
19 Outputs
configuration
confirmation of configuration
The controller allows configuration of active
functions
on
relay
outputs.
Before making the electric connection of
outputs, make sure that their configuration is
correct.
Additionally the installer or manufacturer
must confirm the correctness of outputs
configuration.
Without
following alarm is activated:
settings error, possible settings deletion, and
the recuperator will not work. After applying
installer and manufacturer settings, confirm
settings correctness by choosing Yes in the
Confirm service/manufacturer configuration
parameter of the controller to allow its
operation.
19.1 Outputs configuration for fan
convector
Fan convector is a device with functionality of
both cooler and secondary heater. Controller
has software modules installed, which allow to
control such devices. To turn on fan convector
support go to Manufacturer menu. Under sub-
menu Analog outputs change and change any
function on digital output to Fan convector.
Such modification will delete settings of
outputs 0 – 10 V, that are connected with
cooler and secondary heater control, and will
assign settings of abovementioned devices to
fan convector. From sub-menu Relay outputs
settings it is possible to define additional
signals
controlling
permitting its operation – Fan convector
operation – and signal selecting fan convector
operation
mode
heating/cooling.
Operation
permission
convector mode selection signals must be
mandatorily declared if they are required by
device manufacturer.
To properly configure fan convector function
settings in service menu must be also
amended.
In
sub-menu
and
outputs
and
analog
confirmation,
the
Recuperator
fan
convector:
signal
Fan
convector
signals
and
fan
GHE/Mixer
chamber/Cooler
support parameter and set it to Yes. Then, in
sub-menu Heaters change Secondary heater
type parameter to Analog water or Analog
electric.
Keep
protecting secondary heater remain active
and depending on the selected heater type the
controller will act differently after thermostat
output is activated. In case of secondary
water heater soaking process will start. In
case of electric heater an operation blockade
of secondary heater will activate. Decision of
which heater should be used is made by
person configuring the system.
Incorrectly defined settings may cause fan
convector malfunction or lower heating
comfort in ventilated rooms.
Fan convector function does not have its own
settings, when cooling is needed the controller
cooler settings are used, while heating is
needed
the
declared
settings of controller are used. Controllers
settings can be amended in relevant sub-
menus in Manufacturer menu.

20 Software update

Software update can be performed using only
microSDHC memory card, inserted into the
socket in control panel housing.