Page 1
REGULATOR ecoMAX860P3-C TOUCH FOR AUTOMATIC SOLID FUEL FIRED BOILERS eSTER_x80** eSTER_x40** ecoSTER TOUCH** ecoSTER200** ecoNET300** ecoNET.apk ecoNET.app www.econet24.com functions available additional module B ** the ecoSTER TOUCH or ecoSTER200 room panel, eSTER_x80 wireless room panel or eSTER_x40 wireless thermostat and ecoNET300 Internet module isn’t the standard equipment of the regulator.
Page 2
ELECTRIC DEVICE UNDER VOLTAGE! Before any action related to the power supply (cables connection, device installation etc.) check if the regulator is not connected to the mains! Installation should be done by a person with appropriate electrical qualifications. Improper cables connection could result in the regulator damage.
TABLE OF CONTENTS 12.10 C ......29 ONNECTING EXHAUST SENSOR 12.11 W ......30 EATHER SENSORS CHECKING RECOMMENDATIONS REGARDING SAFETY ..4 12.12 O ......30 PTICAL SENSOR CONNECTION 12.13 M .... 30 IXERS ROOM TEMPERATURE CONNECTION GENERAL INFORMATION ........5 12.14 B ....
dusts or liquids can cause fire or Recommendations regarding safety explosion. Thus, the regulator should be separated from flammable dusts Requirements concerning safety and gases, e.g. by means of an described in detail in individual chapters of appropriate body. this manual. Apart from them, the following requirements should particular...
documentation should be handed over to the General information new user / owner. controller ecoMAX860P3-C TOUCH, Applied symbols hardware version: VACC is a device designed to control the operation of a boiler with In this manual the following graphic symbols automatic feeding of solid fuel with a igniter.
• Fuel level calibration User menu Burner cleaning • Cleaning intensity Main menu • Cleaning start time Information • Cleaning stop time Boiler settings Lambda calibration* HUW settings* Night time decrease boiler Mixer 1-5 settings* • Off, Reduction value, Schedule Summer/Winter Operation with schedule HUW settings*...
The controller support Description of the main window OPERATION Mon. Boiler temperature HUW temperature Legend: 1. Operating modes: FIRE UP, OPERATION, 9. outside temperature value (weather) SUPERVISION, BURNING OFF, functions having influence on preset CLEANING, STOP boiler temperature. Following symbols signal 2.
Attention: Fuel level may be displayed on preset boiler temp. is automatically increased ecoSTER200, ecoSTER TOUCH to load the hot user water tank and power eSTER_x80, eSTER_x40 room thermostat / heating circuits of mixers. panel. FIRE UP Switching On and Off the boiler The FIRE UP mode is for automatic firing up of furnace in boiler.
Parameters of blow-in and exhaust output for Fuzzy Logic mode controller different power levels of the burner are automatically regulates burner power to available in the menu: allow boiler operation in such a way to Boiler settings → Output modulation maintain its temperature on preset level.
during boiler’s pauses (the furnace should Some boilers have an additional grate to not at the same fire up to too high a burn other fuels such as wood waste, etc. To temperature, because it will cause too high a activate the grid, move the parameters temperature of the boiler).
Service settings → Burner settings → Function SUMMER activated Cleaning automatically, on the basis of readings from weather sensor. Use following parameters to 8.12 HUW settings activate this function: The controller regulates temperature of the Summer/Winter → SUMMER Mode → silo of Hot Water HUW, providing that the Auto temperature sensor is connected.
error. room thermostat It is not recommended to use both options at the same time. traditional thermostat (NO-NC), or room panel. Upon activation of the thermostat, the Automatic correction of room temperature is preset mixer circuit temperature will be carried out in accordance with the following decreased, which, if proper decrease value is formula: selected, will stop growth of temperature in...
- floor heating 0,2 -0,6 be reduced automatically, without loss of - radiator heating 1,0 - 1,6 heating comfort reducing fuel - boiler 1,8 - 4 consumption. To activate time intervals, set the parameter Night time decrease for the given heating circuit to ON. The parameter Reduction value temperature...
fuel. If the user does not add fuel, the • Calibration regulator burns all the fuel and switches off To perform calibration - fill the fuel tank to the boiler. the level corresponding to its full load and If the fuel level sensor is not used, the fuel set the parameter: level will be operated in accordance with the Boiler settings →...
if the device is operating correctly and if it is ecoNET.apk (Android) connected properly. Entering manual control is possible only in “Stand-by” mode, when silo is switched off. Manual control Feeder Boiler pump CHW pump Igniter OFF – the device is turned off, ON – the device is turned on.
Conditions of storage and transport Technical data The regulator cannot be exposed to direct Power supply 230V~, 50Hz effects of weather, i.e. rain and sunlight. Storage and transport temperature cannot Current consumed by regulator 0,04 exceed the range of -15…+65°C. Maximum rated current 6 (6) A During transport,...
Disassembly of control panel. To remove the control panel (1) from the Installation of control panel in boiler mounting plate. housing - insert flat elements (2) into indicated slots to release housing catches and remove the panel (1) 12.4 Mounting of module Working module has to be built-into the master equipment.
terminals and conductive (metallic) elements make sure that there is no voltage on of housing (min. 10 mm) is kept. terminals leads, remove Protect connecting wires from tearing, executive module enclosure. loosening and tensioning or built them in in 12.6 Connecting electrical system such a way that no load is exerted on them.
Page 26
All peripherals (such like: pumps, RE-marked relays and connected recipients) may be connected only by qualified persons in accordance with applicable regulations. Safety precautions prevent electrocution should be observed. Regulator should be equipped with a set of pins connected to the 230V AC mains.
12.7 Electric scheme Scheme of electrical connections of the controller: λ –Lambda module, B – additional module, BH – upper buffer temp. sensor type CT4, BL – lower buffer temp. sensor type CT4, PLS - fuel level sensor, T – standard room thermostat type NO-NC, H – voltage output for AL alarm , RELAY –...
Page 28
Scheme of electrical connections of the additional B module: M2, M3 – mixer temp. sensor type CT4, RM2, RM3 – mixer room thermostat, L N PE - electrical power 230V~, GR – grounding strip, PM2, PM3 – mixer pump, SM2, SM3 – mixer servomotor, CPU – controlling, A –...
under the roof. The sensor should not be 12.8 Connection of temperature sensors exposed to direct sunrays and rain. The Sensor wires may be extended using wires of sensor should be installed at least 2 m above cross-section area not less than 0.5 mm the ground far away from windows, chimneys Total length of wires of each sensor should and other sources of heat which could disturb...
T1 (if the ecoSTER TOUCH or eSTER_x80 Service settings → Boiler settings → room control panel is connected): Reserve boiler Service settings → Boiler settings → Deactivating control over additional boiler is Thermostat select done after setting zero value of switching off In order for the room thermostat to control for this parameter.
Note: terminals 22,21,24 have to be galvanically controller cooperates only with insulated from terminals 12,11,14 servomotors of mixing valves equipped with end switchers. Using other servomotors is 12.16 Connection of alarm signalling forbidden. Servomotors with full circle scope controller report alarms of 30 to 255s can be used.
Indicator of valve position is in the menu: 12.20 Connecting of wireless room panel Information. For mixer 1 after some time it The regulator can be equipped with wireless will calibrate automatically. In order to make room panel eSTER_x80 or eSTER_x40, which the valve position indicator displaying quicker can serve as: room thermostat, boiler control the right value, disconnect the electrical...
• Extraction output 13 Service menu Grate* • Blowing power - supervision Service settings • Blowing pause - supervision Burner settings • Fan output - Grate mode Boiler settings • Extraction output - Grate mode CH and HUW settings • Automatic switch to pellet Buffer settings* Lambda sensor*...
Page 35
• CH on • Floor on • Pump only Thermostat selected* Minimum mixer temperature Maximum mixer temperature Proportional range Integration time constant Valve full opening time Pump off by thermostat Mixer input dead zone * Output H Heat exchanger cleaning •...
14 Description of service settings 14.1 Burner Firing-up Time to check whether the burner is already firing up. Only fan is operating. If the • flame has sufficient brightness, it switches to the OERATION mode without the Ignition test time BURNING OFF mode.
Page 37
• Blowing time Duration of blowing when burning off fuel and burning off. • Blowing pause Break between airflows while burning off the fuel in burning off process. • Flame brightness with which airflow starts while burning off the fuel. Blowing start Flame brightness with which airflow starts when burning off the fuel in burning off •...
14.2 Boiler Options to choose from: • Off - deactivates room thermostat influence on boiler operation, • Universal - activates room thermostat for boiler, • ecoSTER T1 - option available after connecting room panel, boiler operation is dependant on room thermostat No1 in ecoSTER, •...
protection in the form of thermostatic valves. Parameter determines how high the boiler temperature will be increased to load HUW container, buffer and mixer cycle. Temperature increase is only realizing when it is necessary. When preset boiler temperature is at sufficient level then Boiler inc.
- allows restricting setting too high mixer preset temperature. Automatic control also will not cause exceeding preset temperature above value set in this parameter. - with parameter Mixer support = Floor ON is also limit temperature of mixer sensor when mixer pump is deactivated. For floor heating set the value below 45º…50ºC or other if producer of materials used for floor or CH installation designer state differently.
Alarm appears when feeder sensor 15 Alarms descriptions damaged or by exceeding measuring scope of this sensor. After alarm the boiler is burnt 15.1 Boiler max. temp. exceeding off. It is necessary to check the sensor and Protection against boiler overheating is done replace it if necessary.
15.4 No communication stale. It consists of a periodic switching on (each 167h several seconds). This The control panel is being linked with the protects the pump against immobilization rest of the electronics with RS485 digital due to scaling. Therefore, during a break in communication link.
• insert memory card (other types Plum Sp. z o. o. In order to load new memory cards are not supported) to a parameters go to: socket in the movable casing of the panel Service settings → [special password] shown above. On the memory card there and choose proper boiler/burner.
20 Possible faults description Symptoms Tips Check: There are no signs of operation ▪ If line fuses are not blown, replace if necessary of device despite connection to ▪ If the wire connecting panel with the executive module is plugged correctly the network.