9 Operation

9.1 Operating mode: ADS-TEC EMS

NOTE
Observe documentation.
For details on the EMS communication interface, see the description "ADS-
TEC EMS_StoraXe Machine Interface".
The control is automated via the local ADS-TEC EMS energy management system for
easy operation and control of the storage system.
Various standard apps are available for the respective applications described in greater detail below.
NOTE
Recommendation for use
9.1.1 Operation
The StoraXe
system is operated via the web browser.
®
With the energy management display in the browser, you can keep an eye on all operating parameters of
the storage system from your PC, notebook, smartphone or tablet. The display provides information on
the usage behaviour of the storage system and presents it in graphical form. All settings for the energy
management system of the battery storage system can be carried out conveniently via this display.

9.1.2 Optimisation of personal consumption

Excess energy from power generators that cannot be used is stored in the battery storage system. This
stored energy can then be discharged to the loads at a later time, e.g., at night or during inclement
weather. As a result, power does not need to be supplied from the public grid or the amount of power that
is supplied is significantly reduced.

9.1.3 Peak-load capping

Peak-load capping is targeted explicitly at end customers who wish to operate the battery storage system
in situations where the electricity rates have a connection and service price. Here, the battery storage
system
is
used
In this case, the storage system is used so as to keep the effective power drawn from the public grid
below the average value within the 15-minute billing interval.
If the system detects that the requirement cannot be met, the "PeakLoadMgr" signal is set.
Configuration
Peak-load capping: Maximum power drawn from the public grid that should not exceed the 15-minute
average.
Peak load power: Definition of the maximum load power.
Page 56 of 72
To be able to use the apps, it is necessary to connect smart meters, depending
on the respective application type.
For this purpose, please refer to the list of supported smart meter models
( Connection and parameterisation of the power meters).
to
cap
peaks
in
the
energy
drawn
GSS0608
Operation
from
the
public
Version: 1.3
grid.