Installation conditions:
The
checklist
( attachment: Transport and preliminary information).
The system is only suitable for outdoor installation.
Observe the following floor space requirements for the system:
− The floor space is to be constructed at the installation location in accordance with the local
conditions and technical data ( 3.2Technical data).
− The floor space is exactly horizontal.
− Cable entry is from below.
− The floor space has the required load capacity for the 1.25 t weight of the system and has to
withstand this load permanently.
If applicable, also take into account the weight of the means of transport.
− Sufficient drainage is available.
Earthing via ring earth electrode for flexible connection cable (min. 16 mm²) according to national
and local regulations and conditions must be in place.
Note that ventilation openings must be kept clear.
− The air at the ventilation openings must be able to circulate freely.
− During the entire operating time, no leaves, dirt, etc. must be sucked in from the ventilation
openings.
Protect the system against penetrating water (groundwater or flood hazard area).
Keep the existing housing doors closed.
Observe the required minimum distances of 1.5 m to adjacent structures. Make additional spacing
allowances for open doors and any escape routes.
When installing in built-up areas, observe the local noise abatement regulations (Germany: "Technische
Anleitung zum Schutz gegen Lärm" (Technical Instructions for Protection against Noise), abbreviated "TA
Lärm"). Observe the resulting minimum distances to residential buildings.
Power connections:
Note the information in the electrical diagram ( Electrical diagram in manual GSS0608).

4.9 Standards

Compliance with the protective aims of the applicable CE directives is confirmed by the EU conformity
declaration and is represented by a CE mark on the product. The EU conformity declaration is part of the
documentation.
Version:1.3
"Commissioning
Requirements"
GSS0608
must
be
completed
and
signed
Page 23 of 72