System Start; System Start For Ems Operating Mode; System Start For Master Operating Mode - ADS-tec StoraXe PowerBooster GSS0608 Manual

Compact storage system
Table of Contents

Advertisement

Commissioning

8.2 System start

8.2.1 System start for EMS operating mode

1. Switch on the main switch.
2. Turn the key switch on the SRC4310 to ON. The LEDs on the SRC4310 switch from red to
green when power is requested in or out of the battery.
3. Switch on the two fuses F10 (air-conditioning system) and F11 (power supply for additional
devices) (next to each other).
4. Close the two system doors.
5. The SRC1420 and air-conditioning system start automatically when switched on.
Note: After shutting down the system, briefly press the START button on the SRC1420 to
restart. The LEDs start to flash. After approx. 3 minutes the system is ready for operation
again.
6. Set the desired application types and parameters via the apps.
Please note the documentation for the StoraXe Machine Interface
( ADS-TEC EMS_StoraXe Machine Interface).
7. ADS-TEC EMS takes over the control of the system.

8.2.2 System start for Master operating mode

1. Switch on the main switch.
2. Turn the key switch on the SRC4310 to ON. The LEDs on the SRC4310 switch from red to
green when power is requested in or out of the battery.
3. Switch on the two fuses F10 (air-conditioning system) and F11 (power supply for additional
devices) (next to each other).
4. Close the two system doors.
5. The SRC1420 and air-conditioning system start automatically when switched on.
Note: After shutting down the system, briefly press the START button on the SRC1420 to
restart. The LEDs start to flash. After approx. 3 minutes the system is ready for operation
again.
6. The system waits for commands from the customer control via Modbus.
Version:1.3
GSS0608
Page 55 of 72

Advertisement

Table of Contents
loading