TPM 083/12

5. Statement of installations

Statement of installations
5.1.
Tab. 5.1.1. Statement of installations
Damper
size
Damper installed on a solid wall construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system
Damper installed on a gypsum wall construction. Space between damper
and wall is filled by mortar, gypsum or another approved fire sealing
Damper installed on a solid ceiling construction. Space between damper
100-400
and ceiling is filled by mortar, gypsum or another approved fire sealing
Duct ended by installation shaft. Space between damper and ceiling is
filled by mortar, gypsum or another approved fire sealing system for
Duct ended by installation shaft. Space between damper and ceiling is
filled by mortar, gypsum or another approved fire sealing system for
Fig. 7
Installation on a solid wall construction
2
1
Position:
1
Fire damper FDMC
2
Mortar or gypsum with min. density 800 kg/m
sealing system for damper installation
Park Allé 366, DK-2605 Brondby
Telefon 70 20 19 11; E-mail:oeland@oeland.dk
FDMC installation
for damper installation.
system for damper installation.
system for damper installation.
damper installation - solid wall construction
damper installation - gypsum wall construction
2
1
3
or another approved fire
8
Classifi-
Figure
cation
EIS 60
7
EIS 60
8
EIS 60
9
EIS 60
10
EIS 60
11