15. Entry into service and revisions

Before entering the dampers into operation after assembly and after sequential revisions, checks
15.1.
and functionality tests of all designs including operation of the electrical components must be
done. After entering into operation, these revisions must be done according to requirement set
by national regulations.
In case that dampers are found unable to serve for their function for any cause, it must be clearly
15.1.1.
marked. The operator is obliged to ensure so that the damper is put into condition in which it is
able to function and meanwhile he is obliged to provide the fire protection another appropriate
way.
Results of regular checks, imperfections found and all-important facts connected with the damper
15.1.2.
function must be recorded in the "FIRE BOOK" and immediately reported to the operator.
Before entering the dampers into operation after their assembly and by sequential checks, the
15.2.
following checks must be carried out.
Visual inspection of proper damper integration, inside damper area, damper blade, contact
15.2.1.
surfaces and silicon sealing.
Inspection hole disassembly: release the covering lid by unscrewing screws. Then tilt remove lid
15.2.2.
from its original position.
Check of blade displacement into the breakdown position "CLOSED" can be done after cutting
15.2.3.
off the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectrical
starting mechanism BAE 72B-S - only FDMC or cutting off the supply from ELECTRICAL FIRE
SIGNALISATION). Check of blade displacement back into the "OPEN" position can be done after
restoration of power supply (e.g. By releasing the RESET button - only FDMC or restoration of
supply from ELECTRICAL FIRE SIGNALISATION).
MANDÍK a.s.
Dobříšská 550
26724 Hostomice
Česká Republika
Tel.: +420 311 706 706
Fax: +420 311 584 810, 311 584 382
E-Mail: mandik@mandik.cz
www.mandik.com
The producer reserves the right for innovations of the product. For actual product information see
Park Allé 366, DK-2605 Brondby
Telefon 70 20 19 11; E-mail:oeland@oeland.dk
www.mandik.com
16
Your distributor

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdmc-srd

Table of Contents