Rack Installation Specifications; Rack Installation Requirements; Placement In The Rack; Table 26 Shelf Installation Order - Fujitsu ETERNUS AX Series Manual

Hide thumbs Also See for ETERNUS AX Series:
Table of Contents

Advertisement

2.

Rack Installation Specifications

This chapter provides the installation specification of the ETERNUS AX/HX.

Rack Installation Requirements

This section explains the requirements for installing the ETERNUS AX/HX in a 19-inch rack.

Placement in the Rack

Note the following when installing the ETERNUS AX/HX in the rack.
Secure a space of 1U at the bottom of a rack.
The space from 2U to 7U is dedicated to PDUs. Since the height of a PDU is 2U, a maximum of three PDUs can
be installed.
Install the controller shelf in 8U.
Drive shelves must be installed in a higher position than the controller shelf.
If size of the drive shelves is mixture of 2U and 4U, the 4U shelves must be installed below the 2U shelves.
The center of gravity must be taken into consideration to prevent a rack from toppling over. Shelves should
generally be installed from bottom to top to lower the center of gravity and to ensure the safe use of racks.
Shelves are installed in the following order (from bottom to top).
Table 26
Installation order
6
5
4
3
2
1
*1:
Uninterruptible Power Supply.
When an AX4100 or HX6100 is ordered together with a rack, drive shelves are installed according to the fol-
lowing priority.
Table 27
Priority
1
2
Shelf Installation Order
DS214C drive shelf
DS224C drive shelf
NS224 drive shelf
DS460C drive shelf
Controller shelf
Controller shelf
Power distribution unit
UPS (*1)
Priority of the Drive Shelf Types Connected to the AX4100
Drive shelf included in the controller shelf
A drive shelf that is different from the one included in the controller shelf
Shelf
Drive shelf
45
Size (height)
2U
2U
2U
4U
2U
4U
2U
-
Site Planning Guide