Configure Time Schedule; Unit Configuration Settings - Daikin iLINQ Quick Start Manual

Table of Contents

Advertisement

Configure Time Schedule

The controller time schedule is used to determine when the unit is considered to be occupied
and unoccupied. The default time schedule is occupied between 7:30 AM and 5:30 PM Monday
through Friday. To modify the schedule, navigate to the Unit → Schedule screen in the
Navigation Menu. Each day of the week has four Schedule Events that are user configurable.
The Schedule Events are composed of a Start Time and an End Time for occupancy. Setting
the Start Time equal to the End Time is considered unoccupied all day. Setting the Start Time to
12:00 AM and the End Time to 11:59 PM is considered occupied all day.

Unit Configuration Settings

Navigate to the Parameters → Configuration screen in the Navigation Menu to verify that the
unit configurations are correct. Many of these settings are set at the factory to match the
unit where the controller is installed but should be confirmed, and others are determined by
site preferences or field-installed options. Additional information on unit configuration
settings is provided in the Daikin iLINQ User Manual.
Changing the Control Mode from DDC to TSTAT configures the controller to accept
commands from a traditional thermostat instead of using the DDC controller application
logic. Follow wiring modification steps outlined in the Daikin iLINQ User Manual.
Setting the Blower Cycling toggle switch to Enabled allows the main blower to be cycled
off during occupied hours when there is no need for cooling or heating for applications
where continuous fresh air ventilation is not required.
If an economizer option has been installed on the unit, verify that the Economizer setting
has been set to Installed or Installed With CO2 as needed.
Setting the Sensor Source selection of a sensor to Network causes the controller to use
the sensor value from the LonWorks
the onboard wiring connections.
DAIKIN ILINQ QUICK START GUIDE
®
or BACnet
®
communication interface instead of
18

Advertisement

Table of Contents
loading

Table of Contents