View Active Alarms

If the controller detects an abnormal condition such as a missing sensor or that the economizer
damper actuator is disconnected, an alarm is generated and can be viewed through the web
interface. View any active alarms by clicking Alarm List in the Navigation Menu. Each alarm
provides a brief description of the alarm and up to two related values that were logged at the
time that the alarm was generated to help determine the cause of the alarm. Active alarms are
highlighted red, and alarms that have been previously cleared are not highlighted. Once the
cause of the alarm has been corrected, the alarm is cleared and the unit resumes normal
operation. If the alarm requires a manual reset, click the Reset Alarms button to clear the alarm.

Test and Balance

During startup, commissioning, or troubleshooting of the unit, it may be necessary to force the
controller into a certain operating mode so that equipment operation can be verified. Navigate to
the Unit → Test/Balance screen in the Navigation Menu to place the unit into Force Mode.
Force Mode allows the user to select from a set of predefined modes. Depending on the Force
Mode selected, the controller commands the necessary outputs based on the unit configuration.