Bacnet Binary Values - ABB FBVi-2U4-4T User Manual

Table of Contents

Advertisement

BACNET BINARY VALUES

POINT SETPOINT
OBJECTNAME
BLOCK
balanceModeLo
45
Yes
fanStatus
88
No
sliderEnable
95
Yes
occOvr
97
No
coolMode
113
No
heatMode
114
No
remoteZoneTempEnb
117
Yes
ventMode
118
No
occMode
120
No
UI1_ZoneTempFailure
124
No
fanAlarm
127
No
occSensorCmd
161
No
CBTStatStptEnb
164
Yes
intScheduleEnb
168
Yes
highCO2Alarm
194
No
lowZoneTempAlarm
196
No
reverseDO09
198
Yes
reverseDO10
200
Yes
reverseDO11
202
Yes
balanceModeHi
204
Yes
reverseAO14
205
Yes
reverseAO15
206
Yes
UI3_DischargeTempFailure
208
No
lowAirFlowAlarm
214
No
lowDischAirTempAlarm
217
No
airflowCalibrationAlarm
219
No
leakingDamperAlarm
221
No
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
FBVi-2U4-4T |
DESCRIPTION
If set to TRUE, Flow will be recorded to
LO_KFactor
If set to FALSE, KFactor will be recorded to
LO_KFactor
If UI4 is set up for a fan status, displays
current fan status.
Enable the sliderSpanStpt (A138) to be used
for UI2.
When the occupied override is active.
Will be On if the unit is in cooling mode.
Will be On if the unit is in heating mode.
Enable the remoteZoneTemp as the active
zone temperature.
Will be On if the unit is in occupied mode.
If UI1 is being used as the active zone
temperature and the temperature reading is
out of range, the alarm will be enabled.
If UI4 is used as the fan status, and the fan is
commanded on and the fan status is open, the
alarm will be enabled.
If an input is set up for an occupancy sensor,
the active status of the occupancy sensor.
CBT-Stat lockout that prevents user
adjustment of setpoints. On = locked out.
Enable the internal BACnet schedule. Disables
occCmd (A269).
If the CO2Demand is above 50% for more than
10 minutes, enable the alarm.
If the active Zone Temperature is below the
active heating setpoint for more than 15
minutes, enable the alarm.
Reverse the operation of digital output DO09
Reverse the operation of digital output DO10
Reverse the operation of digital output DO11
If set to TRUE, Flow will be recorded to
HI_KFactor
If set to FALSE, KFactor will be recorded to
HI_KFactor
Reverse the operation of analog output AO14
Reverse the operation of analog output AO15
If UI3 is used as the active discharge air
temperature and the temperature reading is
out of range, the alarm will be enabled.
If the active airflow is more than 30% below
the active airflow setpoint for more than 5
minutes, enable the alarm.
If the discharge air temperature is more than
15 degrees below the discharge air
temperature setpoint for more than 10
minutes, enable the alarm.
If the active airflow is more than 10% higher
than the maximum cooling flow setpoint for
than 10 minutes, enable the alarm.
If the damper command is at 0% and the
active airflow is above the minHeatFlowStpt
(A230) for more than 10 min, enable the alarm.
APPENDIX: List of
ACTIVE
INACTIVE
DEFAULT VALUES
TEXT
TEXT
IMP STG. MET STG.
On
Off
0
On
Off
0
Enable
Disable
0
On
Off
0
On
Off
On
Off
On
Off
0
On
Off
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
On
Off
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
99