VAV COOLING ONLY VARIABLE SERIES SPEED FAN
TEMPERATURE CONTROL
When the zone temperature is greater than the cooling temperature setpoint, the controller will enter
the cooling mode. The primary airflow rate will be varied between its
maximum Flowrate setpoint
temperature setpoint. Once the zone temperature falls below the cooling temperature setpoint, it will
exit the cooling mode.
When the zone temperature is between the cooling and heating temperature setpoints, it will be in
Deadband or Vent Mode. The controller will maintain the
When the zone temperature falls below the heating setpoint, the controller will enter the heating mode
and the primary airflow rate will maintain the
DAMPER CONTROL
Before the series fan is enabled, the damper will close for 60 seconds to prevent the box fan from
running backwards.
SERIES VARIABLE SPEED FAN
The variable fan speed will be controlled by modulating AO 15 (default 0
required, the fan speed will increase.
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
maxCoolFlowStpt (A228)
as required to maintain the zone at the cooling
minCoolFlowStpt (A227).
FBVI-2U4-4T Contr
FBVi-2U4-4T |
minCoolFlowStpt (A227),
minCoolFlowStpt (A227).
...
10 Vdc). As more cooling is
and its
62