UNIT STATUS AND GRAPHIC POINTS

UNIT STATUS

For information on the current unit function, these points can be enumerated to display on graphic
screens.
Occupancy status is displayed from
0=Unocc
1=Occ
3=Standby
4=SetbackMode
8=SetupMode
Unit status is displayed from
1=CoolMode
2=VentMode
4=HeatMode
HVAC Mode status is displayed from
0 = Auto
1 = Morning Warm Up
2 = Morning Cool Down
4 = Heat Only
8 = Cool Only
16 = Shed
32 = Fire
64 = Purge

GRAPHIC POINTS

Extra points are available for use in graphic generation. These are optional and do not influence the
operation of the unit. Used in Integra applications.
graphic_variableFanSignal (A315)
Use with analog graphics. If
the signal from AO15 is greater than 0, the graphic will be enabled.
graphic_variableFanEnable (D266)
Use with a digital graphic. If
and the signal from AO15 is greater than 0, the graphic will be enabled.
graphic_digitalFan (D261)
Use with a digital graphic. If
digital output DO12 is On, the graphic will be enabled.
graphic_showPerimeterHeat (D265)
Use with a digital graphic. If
graphic_Stg3HeatDigital (D264)
Use with digital graphics. If
graphic will be enabled.
graphic_Stg2HeatDigital (D268)
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
occStatus (A316)
unitStatus (A317)
HVACModeStatus (A295)
fanConfig (A54)
is set up as a variable series fan or a variable parallel fan, and
fanConfig (A54)
is set up as a variable series fan or a variable parallel fan,
fanConfig (A54)
is set up as an on/off series or on/off parallel fan, and
stagesOfPerimeterHeat (A75)
heatConfig (A4)
is set for 3 stages of heat, and digital output DO11 is On, the
Control Sequence
FBVi-2U4-4T |
is greater than 0, enable the graphic.