VAV MODULATING HOT WATER REHEAT SINGLE SPEED FAN

TEMPERATURE CONTROL

When the zone temperature is greater than the cooling temperature setpoint, the controller will enter
the cooling mode. The primary airflow rate will be varied between its
maximum Flowrate setpoint
temperature setpoint. Once the zone temperature falls below the cooling temperature setpoint, it will
exit the cooling mode.
When the zone temperature is between the cooling and heating temperature setpoints, it will be in
Deadband or Vent Mode. The controller will maintain the
If the
activeAirflow (A250)
In heating mode, the controller will maintain the
When the zone temperature falls below the heating setpoint, the controller will enter the heating mode.
If no discharge air temperature sensor is configured is not enabled:
As heating demand rises from 0-100%, the stages of heat shall be enabled to maintain
o
zone temperature setpoints.
If discharge air temperature sensor is configured (this meets ASHRAE Standards):
As heating demand rises from 0-100%, the discharge air temperature shall be reset
o
upwards, to a maximum of 20 deg above zone temperature. The stages of heat shall be
enabled to maintain the discharge air temperature setpoint.
Typically, the modulating heating valve may be controlled by either
state control mode where
additional options available such as having
second stage modulating heat.

DAMPER CONTROL

Before the series fan is enabled, the damper will close for 60 seconds to prevent the box fan from
running backwards.
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
maxCoolFlowStpt (A228)
is below
the minHeatFlowStpt (A230),
minHeatFlowStpt (A230).
drives the hot water valve open and
DO-09
as the first stage modulating heat and AO 15 as the
AO-14
FBVI-2U4-4T Contr
FBVi-2U4-4T |
minCoolFlowStpt (A227),
as required to maintain the zone at the cooling
minCoolFlowStpt (A227).
the heat will be disabled.
or
AO-14
DO-09
drives it closed. There are
DO-10
and its
and
in a tri-
DO-10
75