INPUT CONFIGURATION

The inputs should be configured using the CXProHD BACnet commissioning tool. If changing the
configuration in the field, use these values.
For UI1 Configuration, set
0 = Zone Temperature (default)
1 = Occupancy Sensor
2 = Window Sensor
For UI2 Configuration, set
0 = Temperature Offset 0-5K Ohm (default)
1 = Occupancy Sensor
2 = Window Sensor
For UI3 Configuration, set
0 = Discharge Air Temperature (default)
1 = No discharge Air Temperature
For UI4 Configuration, set
0 = CO₂ Sensor (default)
1 = Humidity Sensor
2 = Occupancy Sensor
4 = Window Sensor
5 = Fan Status
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
UI1Config (A173)
analog setpoint to the following:
UI2Config (175)
analog setpoint to the following:
UI3Config (A176)
analog setpoint to the following:
UI4Config (A174)
analog setpoint to the following:
Installation
FBVi-2U4-4T |
46