Appendix: List Of Fbvi-2U4-4T Points; Hardware Points (I/O); Analog; Digital - ABB FBVi-2U4-4T User Manual

Table of Contents

Advertisement

9

APPENDIX: List of FBVI-2U4-4T points

The
FBVI-2U4-4T
The tables in this Appendix list and describe the points in the
Strategy
type along with the default value in that

HARDWARE POINTS (I/O)

ANALOG

POINT
POINT TYPE
1
Analog Input
2
Analog Input
3
Analog Input
4
Analog Input
8
Analog Input
14
Analog
Output
15
Analog
Output
16
Analog
Output

DIGITAL

POINT
POINT TYPE
09
Digital
Output
10
Digital
Output
11
Digital
Output
12
Digital
Output
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
strategy
is available in both Imperial and Metric units.
OBJECTNAME
UI01
UI02
UI03
UI04
UI08
AO14
AO15
AO16
OBJECTNAME
DO09
DO10
DO11
DO12
FBVi-2U4-4T |
Strategy
and gives the units in each
Strategy
type.
DESCRIPTION
Room/Zone Temperature Sensor
Setpoint Adjust Potentiometer
Supply or Discharge Air
Temperature
CO2, Humidity, or Motion
Detection
Flowrate Sensor
Modulating Heat Stage 1
Modulating Heat Stage 2 or
Variable Fan Speed Control
Damper Commanded Position
DESCRIPTION
Heating Stage 1 or Tri-State
Heating Valve Open
Heating Stage 2 or Tri-State
Heating Valve Close
Heating Stage 3
Series/Parallel On/Off Fan
APPENDIX: List of
IMPERIAL
METRIC
UNITS
UNITS
° F
° C
Ohms
Ohms
° F
° C
Volts
Volts
Pascals
Pascals
%
%
%
%
%
%
Active
Inactive
Text
Text
On
Off
On
Off
On
Off
On
Off
94