7. Connect the power cable to the RTS module and lock the connector with the lock
lever (
Power
cable
socket
FIGURE 2-8
8. Route the power cables from the front of the cabinet beneath or through the
system.
Note – If the power source is overhead, do not route the cables beneath the cabinet.
Instead turn the cables 180˚ degrees and route them back into the cabinet through
the small holes in the bottom of the cabinet (to the left and right of the RTU
assembly). Remove the plastic pop-out covers on the top of the cabinet and route the
power cables though the top of the cabinet.
9. Push the kick-panel and anti-tilt bar back into place.
The retainers on both parts retract and snap into place.
10. Connect the other end of each power cable to the dedicated outlet.
Caution – Each outlet must be a 200–240 VAC, 30A circuit solely for use by that
power cable. The electrical receptacles must be grounded, and the grounding
conductors serving these receptacles must be connected to the earth ground at the
service equipment.