1.5
Connecting Sun Fire V1280/Netra 1280
Power Cables
Caution – The Sun Fire V1280/Netra 1280 system is designed to work with power
systems having a grounded neutral conductor. Do not connect the equipment into
any other type of power system. Contact your facilities manager or a qualified
electrician to determine what type of power is supplied to your building.
Caution – Your Sun product is shipped with grounding-type (three-wire) power
cords. Always connect the cords into grounded power outlets.
Caution – The socket outlets must be installed near the equipment and easily
accessible.
1. Turn the system power switch to the Standby position.
Caution – The On/Standby power switch does not isolate the equipment. The AC
power cords are the primary means of disconnection for this product.
2. Turn the cabinet power off (in a powered cabinet).
Refer to the installation guide that came with the cabinet.
3. Label both ends of the power cords.
Two cords should be labeled Source A and two should be labeled Source B.
4. Connect the power cables to the system.
a. Connect the Source A power cords to AC0 and AC1 on the system and the
Source B power cords to AC2 and AC3 on the system.
b. Run the power cords through the CMA and secure them with tie wraps.
Make sure the CMA can extend and retract without dislodging the power cords.
1-30
Sun Fire E2900 Systems Installation Guide • May 2006