Nominal range
Gauge pressure
0 ... 1.5 psig
0 ... 3 psig
0 ... 6 psig
0 ... 15 psig
0 ... 35 psig
0 ... 70 psig
0 ... 150 psig
0 ... 350 psig
0 ... 900 psig
Absolute pressure
0 ... 15 psi
0 ... 35 psi
0 ... 70 psi
0 ... 150 psi
0 ... 350 psi
Output variable
Output signal
Range of the output signal
HART output values according to HART standard 5.0
Ʋ Primary Value
Ʋ Secondary Value
Signal resolution
Fault signal
Max. output current
Run-up time
Step response time
Additional output parameter - temperature
Integrated resistance thermometer
Tolerance class
Range
Adjustment, external temperature trans-
mitter
The data are an excerpt from the WIKA data sheet TE 32.04. You can find the data sheet under
www.wika.com
VEGAWELL 52 • 4 ... 20 mA/HART Pt 100
Overload capacity, max.
pressure
200 psig
290 psig
430 psig
500 psig
700 psig
950 psig
1300 psig
1900 psig
2900 psig
500 psi
700 psi
900 psi
1300 psi
1900 psi
4 ... 20 mA/HART
3.8 ... 20.5 mA/HART (default setting)
Pressure
Temperature
1 µA
< 3.6 mA; 20.5 mA; 22 mA; unchanged (adjustable via
PACTware)
22 mA
approx. 15 s
≤ 200 ms (ti: 0 s, 0 ... 63 %)
Pt 100 according to DIN EN 60751
B
-50 ... +100 °C (-58 ... +212 °F)
4 ... 20 mA/HART according to -20 ... +80 °C
(-4 ... +176 °F)
10 Supplement
Overload capacity, min.
pressure
-3 psig
-6 psig
-12 psig
-15 psig
-15 psig
-15 psig
-15 psig
-15 psig
-15 psig
0 psi
0 psi
0 psi
0 psi
0 psi
33