Genius Hot-Standby Redundancy Configuration - Emerson PACSystems RX3i User Manual

Genius communications gateway
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User manual
GFK-2892G
18. In PME, store the Hardware Configuration to the RX3i CPU. This act also stores the
The following screenshot shows a completed configuration.
Figure 20: PME Display of Complete Genius Gateway Configuration
3.2.2

Genius Hot-Standby Redundancy Configuration

As shown in Figure 27 below, a Hot Standby system will contain two GCG001 modules. One
uses SBA #31, the other uses SBA#30. Set the SBA as described in step 7 above. Do not select
any SBA other than #30 and #31 for GCG001 in Hot Standby.
Next, be sure to configure each device on the Genius Bus (i.e. those at SBA #1-29) with the
parameter that corresponds to Hot Standby. Use the Genius Hand-Held Monitor (HHM) to
set this parameter.
Configuration
GCG001 configuration data to the PNC001.
Chapter 3
Sep 2019
32

Advertisement

Table of Contents
loading

Table of Contents