Commreq #5: Clear Circuit Fault Command; Commreq #6: Clear All - Emerson PACSystems RX3i User Manual

Genius communications gateway
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User manual
GFK-2892G
6.4.5

COMMREQ #5: Clear Circuit Fault Command

This command is used to clear any faults on a specified circuit of a targeted Genius I/O
device
Command Block for the Clear Circuit Fault Command
Address
Address +1
Address +2
Address +3
Address +4
Address +5
Address +6
Address +7
Address +8
Address +9
6.4.6

COMMREQ #6: Clear All

Circuit Faults Command
The Clear All Circuit Faults command is used to clear all faults on a targeted Genius I/O
device.
COMMREQ/Data_Init_Comm Programming
Command Length
No Wait
Status Block memory
type
Status Block offset
Idle timeout value
Max. communications
time
Command number
PROFINET Device number
Genius Device Number
Relative Circuit Number
4
0
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
Beginning address for the COMMREQ Status Block.
0
0
5
1-255: The device number of the targeted GCG Genius
Gateway.
1-29: the SBA of the targeted Genius Device.
This is the relative number of the circuit within the
Genius device.
It is not its reference number assigned in CPU
Memory. The first circuit on the Genius device is number
1.
For example, to clear faults on discrete I/O block circuit
#5, enter 5 here. For a 4-Input/2-Output analog block,
circuit numbers 1 to 4 are for input channels, 5 and 6 are
for output channels.
Chapter 6
Sep 2019
70

Advertisement

Table of Contents
loading

Table of Contents