Initial connection and configuration

To configure the Gateway, a local connection between a PC/Mac/laptop and
the Gateway needs to be established. The WirelessHART
Emerson 1410H are operationally equivalent and the following instructions
are applicable to both.
Powering the Gateway
For both of the WirelessHART
be needed to power the Gateway by wiring a 10.5–30 VDC (20–30 VDC if a
781 is connected with I.S. barriers to the Emerson 1410D) power source, with
a capacity of at least 250 mA to the power terminals.
Figure 3-1: Emerson 1410H Gateway Housing
A. DIN Rail clip
B. Power light. During normal operation the power indicator will be green.
C. Ethernet port 2. When this port is activated, the factory IP address is
192.168.2.10.
D. Ethernet port 1. Use for standard communication to the webserver or
other protocols enabled on the Gateway. The factory IP address is
192.168.1.10.
E. Emerson 1410 power and serial connection. Black terminal included in the
box.
F. Emerson Wireless 781 Field Link power and data connections. Black
terminal included in the box.