2.4.5

Fault Notifications

Powering up or down or connecting/disconnecting the GCG001 from the controlling
PROFINET device will have effects specific to the controlling device. The discussion below
relates to using the RX3i PROFINET Controller as the controlling device.
Removing a GCG001 from the PROFINET network causes a Loss of Device fault for the
GCG001 itself and all Genius devices connected via that GCG001.
Adding a GCG001 to the PROFINET network causes an Addition of Device fault for the
GCG001 itself and all Genius devices connected via that GCG001.
Note that when a GCG001 is replaced by a successor GCG001, it is important to ensure that
the successor is configured for PROFINET in the same manner as its predecessor. The
quickest way to ensure this is to remove the SD Card from the original and insert it into the
successor GCG001.
2.5
Configuring the Genius Gateway to Operate
with the RX3i CPU
1. Start the PME application, then open or create the project which contains the GCG001
2. Configuring the rack, power supply, CPU and PROFINET Controller in the Project tab
3. Follow the instructions in the PACSystems RX3i & RSTi-EP PROFINET I/O Controller
4. Note that each IO Device connected to the GCG001 will be mapped per the RX3i
2.6

Ethernet Port Connections

As noted earlier, PROFINET IO operates at 100Mbps or higher (full duplex). The GCG001
Genius Gateway cannot operate at a data rate greater than 100Mbps. Thus, for normal
operation, at least one port must be operated at 100Mbps. Other devices operating at
10Mbps may co-exist on that network, though this would not be typical.
Each Ethernet port on the GCG001 module (see Figure 3) operates independently, so
devices that operate at different speeds and/or duplex modes may be attached to the ports.
Each port automatically detects the attached cable and functions properly with either
straight-through or crossover cables.
Note:
Installation
Green, blinking
A Genius Bus error has been detected.
The Genius Bus has failed or no Genius Bus configuration has been
OFF
received.
module.
of the Navigator
Manual GFK-2571, for adding devices to the PROFINET IO Network. The GCG001 will
be one of those devices.
PROFINET Controller configuration.
The module operates only in auto-negotiate mode. All PROFINET devices and switches that
are connected to the module should be configured to use auto-negotiation.
Chapter 2
Sep 2019
24