IDEC HR6S-DN Instruction Manual page 86

Safety module
Hide thumbs Also See for HR6S-DN:
Table of Contents

Advertisement

Diagnostics
LED ERROR - Detected Errors
This LED lights solid in conjunction with additional LEDs to indicate detected errors. In the case of
a detected error, the device transitions to the defined safe state. You must remove the cause of
the detected error and perform a power cycle of the device to exit the defined safe state and
resume operation. Contact your IDEC CORPORATION service representative if the condition
persists.
State
In conjunction with additional
LEDs
Additional LEDs State of
Solid on
STATE,
START and S##
Solid on
STATE,
START and S##
Solid on
POWER
Solid on
STATE
Solid on
START
Solid on
STATE and
START
Solid on
S##
Solid on
S## and S##
86
Meaning
additional LEDs
Flashing
General error detected.
synchronously
Solid on
Configuration error
detected.
Flashing
Power supply error
detected.
Flashing
Error detected at
safety-related output.
Flashing
Cross circuit detected at
start input.
Flashing
Error detected at safety-
synchronously
related output of
extension module.
Flashing
Cross circuit detected at
safety-related input (for
example, incorrect wiring
or application function
with dynamization
selected, but
dynamization not
supported by connected
sensor/device).
Flashing
Cross circuit detected at
synchronously
safety-related inputs (for
example, incorrect wiring
or application function
with dynamization
selected, but
dynamization not
supported by connected
sensor/device).
Remedy
Verify correct wiring.
Verify that the positions of the
selectors are appropriate for the
application to be implemented.
Verify correct wiring.
Use a suitable power supply.
Perform a power cycle.
Verify correct wiring.
Perform a power cycle.
Verify correct wiring.
Verify correct configuration.
Verify correct wiring.
Verify correct configuration.
HR9Z-B2200 8/2020