Electrical Installation

General Information
FIRE, ELECTRIC SHOCK OR ARC FLASH
Disconnect all power from all equipment of your machine/process prior to electrical installation
of the device.
Confirm the absence of power using a properly rated voltage sensing device.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Failure to follow these instructions will result in death or serious injury.
Wiring of the device depends on the safety-related function to be implemented. Before wiring the
device, engineer the safety-related function, perform a risk assessment with regard to your
machine/process, and determine the suitability of the device as well as the connected equipment.
You can wire the device with the terminal blocks in the device or you can remove the terminal
blocks. For the latter, pull the terminal blocks out of the device, connect the individual terminals and
push the terminal blocks back into the device.
Use 75 °C (167 °F) copper conductors to wire the device.
Wire Cross Sections, Stripping Lengths, and Tightening Torques
Characteristic
Stripping length for Push-in terminals
Stripping length for screw terminals
Wire cross section, single wire without wire ferrule
Wire cross section, single wire with wire ferrule
Wire cross section, two wires without wire ferrule
Wire cross section, two wires with uninsulated wire
ferrule
Wire cross section, two wires with insulated wire
ferrule
Tightening torque for screw terminals
(1) Stranded or solid
HR9Z-B2200 8/2020
DANGER
Value
12 mm (0.47 in)
7 ... 8 mm (0.28 ... 0.31 in)
(1)
2
0.2 ... 2.5 mm
(24 ... 12 AWG)
2
0.25 ... 2.5 mm
(1)
2
0.2 ... 1.5 mm
(24 ... 16 AWG)
2
0.25 ... 1 mm
(24 ... 18 AWG)
2
0.5 ... 1.5 mm
(20 ... 16 AWG)
0.5 ... 0.6 N m (4.4 ... 5.3 lb in)
(24 ... 12 AWG)
Installation