Trane IntelliPak with Symbio 800 Installation, Operation And Maintenance Manual page 51

Commercial rooftop air conditioners
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Table 17. Outside air damper travel adjustment
Outside Air Damper
Crank Arm Hole
Configuration
Position
1
1 - 3
2
1 - 4
3
1 - 6
4
2 - 5
5
2 - 7
6
2 - 8
Table 18. Outside air damper pressure drop — No Traq™
CFM
#1
4000
0.06
6000
0.11
7000
0.14
8000
0.18
9000
0.22
10000
0.27
11000
0.32
12000
0.37
13000
0.43
8000
0.17
10000
0.25
12000
0.36
14000
0.48
16000
0.62
18000
0.78
20000
0.95
22000
1.14
24000
1.34
RT-SVX063G-EN
Return Air Damper Crank
Arm Hole Configuration
90°
9 - 11
90°
75°
9 - 12
75°
60°
9 - 13
65°
40°
10 - 14
40°
31°
20°
No Traq™
Outside Air Damper Position
#2
#3
20, 25 and 30 Ton
0.07
0.08
0.14
0.17
0.21
0.25
0.28
0.35
0.36
0.46
0.45
0.58
0.56
0.72
0.67
0.88
0.80
1.05
40, 50 and 55 Ton
0.34
0.40
0.47
0.56
0.60
0.73
0.75
0.93
0.92
1.15
1.09
1.38
1.28
1.64
1.49
1.92
1.71
2.22
#4
#5
0.16
0.24
0.36
0.60
0.49
0.83
0.65
1.11
0.83
1.42
1.02
1.78
1.24
2.17
1.48
2.60
1.74
-
0.84
1.69
1.24
2.48
1.72
-
2.28
-
2.91
-
-
-
-
-
-
-
-
-
Installation
#6
0.87
2.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
51

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IntelliPak with Symbio 800 and is the answer not in the manual?

Table of Contents