Connecting the Gas Supply Line to the
Furnace Gas Train
Follow the steps below to complete the installation between
the supply gas line and the furnace. Refer to the following
figures, for the appropriate gas train configuration.
1. Connect the supply gas piping using a "ground-joint"
RT-SVX063G-EN
Flue Vent
Heat access
(850 MBH shown)
Gas pipe
Combustion
entry with
inlet rain shield
grommet CPVC Drain
(40-75 ton only)
A
B
6.75
7.59
6.75
11.85
6.75
11.85
10.5
18.0
10.5
13.35
A
B
C D
C
D
5.29
7.85
5.42
11.58
5.42
11.58
5.42
11.58
5.42
11.58
type union to the furnace gas train and check for leaks.
2. Adjust the inlet supply pressure to the recommended 7"
to 14" w.c. parameter for natural gas (11" to 14" w.c. for
propane).
3. Ensure that the piping is adequately supported to avoid
gas train stress.