baltur TBG 35 MC Instruction Manual For Installation, Use And Maintenance page 53

Two-stage progressive / modulating gas burners
Table of Contents

Advertisement

Available languages

Available languages

SERVOMOTOR CAMS SQN72.4D5A20 FOR TBG...MC REGULATION
2
I
2nd flame air regulation cam (120°)
II
Total air closure (burner stopped) (0°)
III 1st flame air regulation cam (10°)
IV Ignition air cam (30°) IV > III
V
Ignition transformer cam (40°)*
* Cam V > IV (Approx. 5 - 10°)
1
3
1
Motor-camshaft coupling On/Off pin
2
Reference scale
3
Position indicator
4
Adjustable camshaft
Use the corresponding rings to modify the adjustment of the utilized
cams (I - II - III....). The index of the ring indicate on the respective
reference scale the rotation angle taken up for each cam.