6-2-3

CX-Programmer Connection

Use the following procedure if the CX-Programmer cannot connect to the PLC.
Connecting via the Peripheral USB Port
The CX-Programmer
cannot connect.
Is the USB cable
securely connected?
Yes
Is the CX-Programmer
network type set to USB?
Yes
Replace the USB cable.
If the cycle time is too long, it may result the communication failure when CX-Programmer tries to work
online. In this case, click the Settings button on the right side of Network Type in the Change PLC dia-
log box and increase the value in Response Timeout(s).
CP2E CPU Unit Hardware User's Manual(W613)
No
Insert the cable all the way in at both the
personal computer and at the CPU Unit.
Can the CX-
No
Programmer be
connected online?
No
Set the CX-Programmer network
type to USB.
Can the CX-
No
Programmer be
connected online?
Yes
End
Yes
6 Troubleshooting
6-23