Emc Compliance (Iec/En 61800-3); Definitions; Category C3 - ABB ACS580-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS580-04:
Table of Contents

Advertisement

WEEE mark
At the end of life the product should enter the recycling system at an appropriate collection
point and not placed in the normal waste stream.

EMC compliance (IEC/EN 61800-3)

Definitions

EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or system
within its locality.
First environment includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not supplying
domestic premises.
Drive of category C1: drive of rated voltage less than 1000 V and intended for use in
the first environment.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed
and started up only by a professional when used in the first environment.
Note: A professional is a person or organization having necessary skills in installing
and/or starting up power drive systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in
the second environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current
equal to or above 400 A, or intended for use in complex systems in the second
environment.

Category C3

The drive complies with the standard with the following provisions:
1.
The drive is equipped with EMC filter (+E210) and common mode filter (+E208).
2.
The motor and control cables are selected as specified in the hardware manual.
3.
The drive is installed according to the instructions given in the hardware manual.
4.
Maximum motor cable length is 100 m (328 ft).
5.
The value of parameter 97.01 is set to 2 kHz or less.
WARNING!
A drive of category C3 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is
expected if the drive is used on such a network.
Technical data 195