This guide tells you briefly how to install the drive module into a 800 mm wide Rittal TS 8 cabinet. For installation examples in different cabinets and more detailed instructions, engineering guide lines, technical data and complete safety instructions, see the hardware manual (www.abb.com/drives: Select Document Library and search for document number 3AXD50000035191 [English]). Obey the safety instructions See figures on page 9.
4 EN – Quick installation guide 5. Measure that the installation is de-energized. • Use a multimeter with an impedance of at least 1 Mohm. • Make sure that the voltage between the drive module input power terminals (L1/U1, L2/V1, L3/W1) and the grounding (PE) busbar is close to 0 V. •...
Page 5
EN – Quick installation guide 5 constant pressure with one foot on the base of the module to prevent the module from falling on its back 3AUA0000088632 • Unfasten the insertion ramp and attach the LCL filter module to bottom plate. •...
Page 6
6 EN – Quick installation guide Step Task (motor cables) Screw in and tighten the insulators to the drive module by hand. Install the T3/W2 connection terminal to the insulators. WARNING! Do not use longer screws or bigger tightening torque than given in the installation drawing.
Page 7
EN – Quick installation guide 7 Default I/O connections The default I/O connections of the Factory macro of the ACS880 primary control program are shown below. Wire sizes and tightening torques of the control board terminals: 0.5 … 2.5 mm (24…14 AWG) and 0.5 N·m (4 lbf·in) for both stranded and solid wiring.
Page 8
8 EN – Quick installation guide Relay outputs XRO1…XRO3 Ready 250 V AC / 30 V DC Running 250 V AC / 30 V DC Faulted(-1) 250 V AC / 30 V DC Fault External power input XPOW 24 V DC, 2 A +24VI Reference voltage and analog inputs J1, J2, XAI...
Page 9
Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 9 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet (PE) (PE) Drive type Air flow Losses Type DIN 43653 ACS880-34- = 400 V 246A-3 2100 5280 170M5408 293A-3 2100...
Page 10
10 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Rittal TS 131 800 Rittal TS 8612.580 Tapping screw M6×12 Torx T30 8 N·m 360 °...
Page 11
Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 11 Tapping screw M6×12 Torx T30 (Hex) 8 N·m Combi screw M8×30 Hex 20 N·m...
Page 12
12 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Combi screw M4×8 Torx T20 2 N·m Combi screw M4×8 Torx T20 2 N·m Combi screw M4×8 Torx T20 2 N·m...
Page 13
Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 13 M6 Serpress 8 N·m M6 Serpress 8 N·m Screw M10×30 and washer Combi screw M8 Combi screw M8 24 N·m 24 N·m...
Page 14
14 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Combi screw M12×25 70 N·m Screw M10×30 -> FAN3:LCL Combi screw M4×8 Torx T20 2 N·m Combi screw M4×8 Torx T20 2 N·m...
Page 15
Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 15 Combi screw M12×25 Hex (Delta) 70 N·m 8 N·m Combi screw M6×12 Torx T25 8 N·m...
Page 16
16 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet...
Page 17
Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 17 Combi screw M4×10 Torx T20 2 N·m Combi screw M6×20 Torx T25 2 N·m Combi screw M6×20 Torx T25 2 N·m...
Page 18
18 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Hex screw M12×35 full thread 70 N·m Hex nut M12 70 N·m...
Page 19
Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 19 Combi screw M4×10 Torx T20 2 N·m Combi screw M4×10 Torx T20 2 N·m Combi screw M6×20 Torx T25 2 N·m...
Page 20
20 Step-by-step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Tapping screw M6×12 Torx T30 (Hex) 8 N·m...
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
Page 22
Contact us www.abb.com/drives www.abb.com/drivespartners 3AXD50000212453 Rev A (MUL) 2018-03-23...