Grounding System Compatibility Check - Iec, Not North America; Emc Filter Compatibility; Ground-To-Phase Varistor Compatibility - ABB ACS580-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS580-04:
Table of Contents

Advertisement

1.
Stop the drive and do the steps in section
before you start the work.
2.
Make sure that the resistor cable is connected to the resistor and disconnected
from the drive output terminals.
3.
At the drive end, connect the R+ and R- conductors of the resistor cable together.
Measure the insulation resistance between the conductors and the PE conductor
with a measuring voltage of 1000 V DC. The insulation resistance must be more
than 1 Mohm.
ohm
Grounding system compatibility check – IEC, not North
America
This section is valid for the IEC drive types.
Frame
R10, R11

EMC filter compatibility

The drive has an internal EMC filter (+E210) as standard. You can install the drive with
the EMC filter connected to a symmetrically grounded TN-S system, IT system,
corner-grounded delta, mid-point-grounded delta and TT system.
Note: If you disconnect the EMC filter, the electromagnetic compatibility of the drive
decreases.

Ground-to-phase varistor compatibility

The drive is equipped with an internal ground-to-phase varistor as standard. You can
install the drive with the ground-to-phase varistor connected to a symmetrically
grounded TN-S system, corner-grounded delta and mid-point-grounded delta system.
If you install the drive to an IT system or a TT system, you need to disconnect the
varistor. See section
Ground-to-phase varistor disconnecting instructions – IEC, not
North America (page
281).
1000 V DC,
> 1 Mohm
Default wires – Global (IEC) except North America
EMC
Connected
Electrical installation 103
Electrical safety precautions (page 21)
R+
R-
PE
VAR
Connected
11