Energy efficiency data (ecodesign)

Energy efficiency data according to IEC-61800-9-2 is available from the ecodesign tool
(https://ecodesign.drivesmotors.abb.com).

Protection classes for module

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL
50/50E)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)

Ambient conditions

Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Installation site altitude
IP00 (standard)
IP20 (option +B051 and bottom grille installed)
UL Open Type
III
I
Operation
For TN and TT neutral-
grounded network sys-
tems and IT non-corner-
grounded network sys-
tems: 0 ... 4000 m
(13123 ft) above sea level
For TN, TT and IT corner-
grounded network sys-
tems: 0 ... 2000 m
(6561 ft) above sea level
Above 1000 m (3281 ft):
refer to the derating in-
formation
Storage
in the protective package
-
Technical data 191
Transportation
in the protective package
-