Electrical Connection - TESTO 6448 Instruction Manual

Compressed air counter probe
Hide thumbs Also See for 6448:
Table of Contents

Advertisement

4 Initial operation
4.2.

Electrical connection

The instrument may only be installed by a qualified electrician.
Follow the national and international regulations regarding the
installation of electro-technical systems. The voltage supply is to be
laid out in accordance with EN50178, SELV, PELV. To meet the
"limited voltage" requirements according to UL 508, the instrument
must be supplied from a galvanically isolated source and protected
against short-circuits by means of an overcurrent device.
Four-wire pin assignment (not an accessory)
If the optional connecting cable for electrical isolation is not used,
then the following assignments apply.
Pin assignment on the connector (M12x1)
Pin no.
1
2
3
4
1 x switching output, 1 x analogue output (condition on delivery)
The
OUT1
OUT2
configuration in which the sensors are delivered.
Pin assignment on the instrument
Pin assignment on the cable connector
Pin no.
1
2
3
4
24
Wire colour
Brown
White
Blue
Black
output is used as a PNP signal output (pulse) and the
output is used as an analogue output. This is the
Wire colour
BN (brown)
WH (white)
BU (blue)
BK (black)
Assignment
+L (18...30V DC)
OUT2
0 V DC (GND)
OUT1